One Way Fire Rated Walls
        HardieSmart™ Boundary Wall System Component Description
External Face of Wall
- 1 layer of James Hardie minimum 6mm external cladding
 - James Hardie HardieWrap™ weather barrier (refer to technical data sheet for suitability)
 
Internal Face of Wall
- 1 layer of minimum 6mm James Hardie® internal lining (if using Architectural™ linings, Villaboard® lining must be fixed behind.
 
Wall Frame
- 90x45mm seasoned timber studs
 - 90x35mm seasoned timber studs can be used with a reduced maximum load capacity of 3.4kN/stud for load bearing walls when used at 600mm centres
 
Insulation
- James Hardie HardieFire™ Insulation
 
        60/60/60 FRL Option 2 (JH-218)
NOTE: Where a fire and water resistant plasterboard is specified only Boral or Lafarge must be used.
External Face of Wall
- 1 Layer of James Hardie minimum 6mm thickness external cladding
 - James Hardie HardieWrap™ weather barrier (refer to HardieWrap™ Technical Data Sheet for suitability).
 - 16mm fire and water resistant plasterboard lining
 
Internal Face of Wall
- 1 Layer of standard 10mm plasterboard lining
 
Wall Frame
- Minimum 90x45mm seasoned timber studs up to 2.7m high.
 - Minimum 92x35x1.15 steel studs with 1.350mm horizontal noggings up to 3m high.
 
Thicker studs are needed:
- For higher walls, refer to the fire and acoustically rated design manuals.
 - At sheet joins, refer to the relevant product manual for clarity.
 
        60/60/60 FRL Option 3 (JH-219)
NOTE: Where a fire and water resistant plasterboard is specified only Boral or Lafarge must be used.
External Face of Wall
- 1 Layer of James Hardie minimum 6mm thickness external cladding
 - James Hardie HardieWrap™ weather barrier (refer to HardieWrap™ Technical Data Sheet for suitability).
 - 13mm fire and water resistant plasterboard lining
 
Internal Face of Wall
- 13mm fire resistant plasterboard lining
 
Wall Frame
- Minimum 90x45mm seasoned timber studs up to 2.7m high.
 - Minimum 92x35x1.15 steel studs with 1.350mm horizontal noggings up to 3m high.
 
Thicker studs are needed:
- For higher walls, refer to the fire and acoustically rated design manuals.
 - At sheet joins, refer to the relevant product manual for clarity.
 
        90/90/90 FRL (JH-21.10)
NOTE: Where a fire and water resistant plasterboard is specified only Boral or Lafarge must be used.
External Face of Wall
- 1 Layer of James Hardie minimum 6mm thickness external cladding
 - James Hardie HardieWrap™ weather barrier (refer to HardieWrap™ Technical Data Sheet for suitability).
 - 16mm fire and water resistant plasterboard lining
 - 6mm HardieFlex lining
 
Internal Face of Wall
- 16mm fire and water resistant plasterboard lining
 
Wall Frame
- Minimum 90x45mm seasoned timber studs up to 2.7m high.
 - Minimum 92x35x1.15 steel studs with 1.350mm horizontal noggings up to 3m high.
 
Thicker studs are needed:
- For higher walls, refer to the fire and acoustically rated design manuals.
 - At sheet joins, refer to the relevant product manual for clarity.